Summary
If a sensor is created and commissioned without a monitor restart, it may end up in a state where it is not loaded correctly into the monitor memory. This will cause the monitor only to be able to process the acceleration measurements from the sensor.
Solution
Restart the monitor, and it will force it to reload all sensors into memory and resolve the issue. Allowing measurements to be stored the next time they arrive from the sensor.